    Evaluation of lightning performance in subtransmission line 69 kv on electrical monopole

    Thumbnail
    View/Open
    ENG_60_03.pdf (6.592Mb)
    Date
    2021-01-31
    Author
    Songsang, Arnon
    อานนท์ ส่งแสง
    Metadata
    Show full item record
    Abstract
    Most of Metropolitan Electricity Authority (MEA) electric power system is using overhead line. It is 94% in the system including subtransmission, distribution and low voltage system. All of them were installed on concrete pole. At present, many public facilities have been built such as Sky-Train. It causes more constrains for construction with concrete pole due to lack of right of way. MEA needs to using electrical monopole plays an important role. It’s easier than concrete pole for construction and it requires less construction area than concrete pole. The thesis evaluation of lightning performance in subtransmission line 69 kV study on MEA. Case lightning strike on overhead ground wire (OHGW) at pole top of electrical monopole with suspension insulator, Focusing on three factors is pole top voltage, critical current and back flashover rate (BFOR). ATP-EMTP software is used for simulation. The results show that BFOR is reduced by 79% on electrical monopole structure with suspension insulator compared with existing concrete pole. BFOR is also reduced by 33.17% on concrete pole with external ground wire. The results could be served as a guideline in subtransmission line design and improvement in MEA power system.